In Portugal, fire extinguishers must be serviced every 12 months by an entity registered with ANEPC (the national civil protection authority) whose extinguisher service is certified to NP 4413. Missing a deadline, or using an uncertified provider, is a minor economic offence. For a facilities or maintenance team, the hard part is rarely the rule. It is keeping hundreds of units, across several sites, inside their dates with the paperwork to prove it. This guide sets out what the rules require, what a service visit covers, how to vet a provider and how to run the whole cycle as a scheduled, documented routine.
Resumen
- Annual maintenance under NP 4413 is the base obligation, with a one-month tolerance either side of the interval.
- Routine charging is every five years for water, foam and powder units and every ten years for CO₂ units; any use, total or partial, requires a recharge.
- The provider must be registered with ANEPC and hold an NP 4413 extinguisher-maintenance certificate. Using one that does not is itself an offence.
- Keep the label, the service report and the provider’s credentials linked to each extinguisher, so that an inspection or tender audit takes minutes.
- Treat each extinguisher as a recurring work order with its own due date, location and evidence.
Índice
- What the law requires
- The NP 4413 calendar in plain terms
- What a service visit covers
- Choosing a provider you can defend in an audit
- Labels, reports and records
- What does maintenance cost?
- Running the cycle as a scheduled routine
- Perspectiva
- Bringing it into FullyOps
- PREGUNTAS FRECUENTES
- Fuentes
What the law requires
Two pieces of legislation frame the obligation: Decreto-Lei n.º 220/2008, which sets the fire safety regime for buildings, and its technical regulation, the RT-SCIE. Decreto-Lei n.º 9/2021 of 29 January attaches the penalties: overdue maintenance or validity periods, and maintenance by a service without NP 4413 certification, are sanctionable as economic misdemeanours.
The practical consequence is that two separate failures count: a missed date and a wrong provider. A perfectly timed service carried out by an uncertified company does not protect the owner or operator.
We found no change to service or charging intervals announced in the last two years in the official sources. The framework you work to today is still annual NP 4413 maintenance by a certified service, with the provider registered with ANEPC.
The NP 4413 calendar in plain terms
NP 4413 is the Portuguese standard for extinguisher maintenance. Its intervals are what you build your schedule on:
| Intervention | Interval | Source detail |
|---|---|---|
| Technical maintenance by a certified provider | Every 12 months, with one month of tolerance before or after | NP 4413:2012 |
| Routine charging, water, foam and powder extinguishers | Every 5 years | NP 4413:2012 |
| Routine charging, CO₂ extinguishers | Every 10 years | NP 4413:2012 |
| Recharge after use | After any total or partial discharge | Azores Civil Protection Authority manual |
The 12-month interval runs from the date of charging, and it may not exceed one year from manufacture. The standard also calls for earlier intervention when the condition of the agent or the equipment warrants it.
Un ejemplo práctico
A facilities firm manages a logistics warehouse with 60 powder extinguishers, all charged on 10 March. The annual service window runs from 10 February to 10 April of the following year. If the provider only reaches the site on 20 April, all 60 units are overdue. The five-year charge falls on the same March date, so in year five the annual visit and the recharge are best planned as one job. When one unit is discharged in October, it needs a recharge at once, and its own cycle then restarts from the new charge date, which will no longer match the other 59.

This is where spreadsheets fail. Units drift out of step with each other after every discharge, replacement or relocation.
What a service visit covers
NP 4413 distinguishes two levels of attention.
Routine checks are quick inspections by the person the owner or operator designates. The standard says they may be done by the safety responsible person or contracted to a certified maintenance company. The Azores Civil Protection Authority’s training manual describes this as a quick check, as opposed to the detailed technical maintenance done by an authorised company.
A routine check typically looks at whether the unit is in place, visible and accessible, whether the seal is intact and whether the pressure indicator, where fitted, is in range.
Technical maintenance is the annual intervention. According to NP 4413, it includes checking:
- the exterior condition against the rejection criteria;
- the maintenance label and the charge date;
- seals, pressure and weight;
- the hose and diffuser;
- the relevant internal parts.
The provider then records the intervention on the label. After any total or partial use, the extinguisher must be recharged by qualified personnel.
The sources do not set a single universal trigger for repair versus replacement beyond the standard’s rejection criteria and the applicable service-life limits. In practice the provider’s report tells you which units failed, and your replacement is then a purchase and a new work order, not a judgement call made in the corridor.
Choosing a provider you can defend in an audit
Because an uncertified service is an offence in itself, verify the provider before the first visit and again whenever the contract renews. Check three things.
- ANEPC registration. Registration is mandatory for entities that sell, install or maintain SCIE equipment covered by Portaria n.º 773/2009, as amended by Portaria n.º 208/2020. SCIE is the Portuguese acronym for fire safety in buildings.
- An NP 4413 certificate. For extinguisher maintenance, ANEPC requires the entity to hold a certificate issued by a certification body. An ISO 9001 certificate is optional and does not replace it.
- A named technically responsible person. ANEPC says the entity must identify at least one technically responsible person, whose technical competence must be recognised. NP 4413 initial or continuous training can count towards the extinguisher-specific part of that training, while general training is still required.
File copies of the certificate and the registration against the supplier record, with their expiry dates, so renewal checks do not depend on someone’s memory.
Labels, reports and records
NP 4413 requires the maintenance label to stay legible and in good condition, including the charge date, and the procedure records each intervention on it. The Azores manual also describes a report of the work performed. The sources reviewed do not set a single statutory retention period for service reports kept by the customer. A sensible policy is to keep every report for at least as long as the extinguisher stays in service, and for as long as your contracts or insurers require.

What an inspector, an insurer or a tender evaluator asks for is usually the same: which units exist, where they are, when each was last serviced, by whom, with what result. Our guide on registros de cumplimiento del mantenimiento para inspecciones y licitaciones en Portugal covers how to structure that evidence, and a four-photo sequence is a quick way to make each visit’s record hard to dispute: the unit in place, the label, the seal and the pressure reading.
What does maintenance cost?
Annual service is normally quoted per unit, and the price moves with a handful of factors:
- Extinguisher type and size: powder, CO₂, foam and water units, and 2 kg versus 6 kg or larger, involve different work and materials.
- Which intervention is due: a plain annual check costs less than a five-year recharge or a replacement part.
- Volume and number of sites: more units per visit and a tidy route reduce the cost per unit.
- Condition: hoses, seals, labels, signage or brackets that need replacing add to the bill.
- Access and travel: remote sites and difficult locations raise the visit cost.
For orientation only, a 2026 price guide on the Habitissimo marketplace lists per-unit prices ranging from €45 to €180 for extinguisher services, depending on the work. Your own quote, for your own mix of units, is what counts.
The lever that is entirely in your hands is the one that stops money being wasted: knowing exactly how many units are due, where, and in which window. That lets you ask for one consolidated quote per site and per year, instead of reacting unit by unit.
Running the cycle as a scheduled routine
A compliant extinguisher programme is, in essence, a preventive maintenance plan with legal deadlines. Here is the routine, step by step, and where each step usually goes wrong.
- Build the register. One record per extinguisher: type, capacity, serial number, location, manufacture date, last charge date, next service date, next five- or ten-year charge. Where it goes wrong: units added or moved without updating the list. In FullyOps the register sits alongside your other assets, with the same asset lifecycle view you use for the rest of your equipment.
- Set the recurring jobs. Create a preventive schedule for the annual service with a window of one month either side, and a separate date for the routine charge. Our platform handles preventive maintenance scheduling and work order management, so each due date becomes a work order assigned to a person, rather than a line in a spreadsheet. See also our overview of maintenance calendar software for how to structure the calendar.
- Run the routine checks internally. Your designated person walks the route, records the result and flags problems. Technicians can capture this in the field and the data lands in the same system. Where it goes wrong: checks done but never recorded.
- Book the certified service. Send the provider the list of units due, in their window. Attach the provider’s ANEPC registration and NP 4413 certificate to the supplier record.
- Close the job with evidence. Attach the service report and the photos, update the charge date and generate the next work order. Our flujo de órdenes de trabajo en cinco etapas shows how a job is closed so that nothing is left half-documented.
- Handle discharges and replacements at once. A used unit becomes a recharge work order the same day. Where stock of replacement units is held, inventory tracking shows what is available on each site.
- Report. Pull a list of units by site, due date and status before an inspection, an insurance renewal or a tender submission.
Perspectiva
Extinguisher maintenance looks like a small job until you multiply it. One unit is a label and a date. Four hundred units across eleven sites, each with its own charge date that shifts after every discharge, is a scheduling and evidence problem.
We built FullyOps to bring asset lifecycle, work order control, analytics and real-time field data collection into one platform for industrial, facility and maintenance teams. That fits this obligation well. The deadline is fixed by law, the provider has to be verified, and the proof has to be there when someone asks for it.
For operations managers, the benefit is visibility: every due date is a work order with an owner, and every closed job carries its report and photos. For technicians, it is a clear list for the route and a quick way to record what they found. For administrators, user roles and permissions control who can close a job or change a record.
The legal rule does not change with the software. What changes is how much of your week goes on chasing it.
Pedro
Bringing it into FullyOps
If you manage extinguishers alongside other equipment, the simplest approach is to keep them in the same system as everything else you maintain. FullyOps offers work order management, preventive maintenance scheduling, inventory tracking, reporting and integrations with other systems, in Basic, Professional and Advanced plans for technicians, administrators and managers. You can see the plans on the FullyOps homepage and ask for a demo there.
PREGUNTAS FRECUENTES
How often must fire extinguishers be maintained in Portugal?
Annually. NP 4413 sets a 12-month interval with a tolerance of one month before or after. On top of that, water, foam and powder units are charged routinely every five years and CO₂ units every ten years.
Who is allowed to maintain an extinguisher?
An entity registered with ANEPC, with an extinguisher-maintenance service certified to NP 4413 and at least one identified technically responsible person. Your own staff can carry out the routine checks, but the technical maintenance belongs to the certified provider.
What happens if maintenance is overdue?
Overdue maintenance or validity periods are classed as minor economic offences under Decreto-Lei n.º 9/2021, and so is maintenance by a service that lacks NP 4413 certification. Keeping each unit’s due date and the provider’s credentials on record is the way to stay clear of both.
Do I need to recharge an extinguisher after a partial discharge?
Yes. An extinguisher that has been used, fully or partially, must be recharged by qualified personnel. Raise the recharge as a job the same day so the unit is not left on the wall empty.
What records should I keep?
Keep the maintenance label legible, with the charge date, together with the provider’s service report for each unit and the provider’s ANEPC registration and NP 4413 certificate. Linking all of these to the individual extinguisher makes audits quick.
Fuentes
- Decreto-Lei n.º 9/2021, de 29 de janeiro, Diário da República
- NP 4413:2012, Norma de Manutenção de Extintores
- ANEPC, registo de entidades, perguntas frequentes
- ANEPC, entidades de equipamentos e sistemas
- Autoridade Regional de Proteção Civil dos Açores, Manual M1I (2019)
- Habitissimo, preços de manutenção de extintores